Numerical Simulation of Mechanical Ventilation and CO Distribution in Underground Garages

Sifan Zhou
Frontiers in Sustainable Development, (2026), Vol.6, No.5, pp.32-37
Published: May 25, 2026
DOI: 10.54691/v60vwn11
PDF: Download Full Text PDF
Abstract

This study investigates the CO concentration distribution and airflow characteristics in a residential double-level underground garage under different ventilation conditions using numerical simulation. The realizable k-ε turbulence model was employed with the SIMPLE algorithm for iterative solution. Results show that natural ventilation is insufficient to effectively control pollutant levels, with CO distribution being significantly non-uniform. Under mechanical ventilation, increasing the air change rate enhances airflow uniformity, reduces CO concentrations from 6.4 to 9.6 ppm to 3.2 to 6.4 ppm, and improves pollutant removal efficiency. The findings provide practical guidance for ventilation system design in underground garage environments.

Keywords: Underground Garage; CO Distribution; Numerical Simulation; Mechanical Ventilation.
APA Citation: Sifan Zhou (2026). Numerical Simulation of Mechanical Ventilation and CO Distribution in Underground Garages. Frontiers in Sustainable Development, 6(5), 32-37. https://doi.org/10.54691/v60vwn11

References

  1. F. Alshoobi, P. Taber, H. Deng. Effects of cross level air interaction within multilevel underground carparks on indoor air quality. Fluids, vol. 5 (2020) No. 4, p. 177.
  2. A. Faramarzi, J. Lee, B. Stephens, M. Heidarinejad. Assessing ventilation control strategies in underground parking garages. Building Simulation, vol. 14 (2021) No. 1, p. 55–70.
  3. C. Jia, J. Zhao, X. Li, et al. Numerical simulation of the ventilation and fire conditions in an underground garage with an induced ventilation system. Buildings, vol. 13 (2023) No. 8, p. 2074.
  4. M. Krarti, A. Ayari. Ventilation for enclosed parking garages. ASHRAE Journal, vol. 43 (2001) No. 2, p. 52–56.
  5. C-R. Chu, Z-Y. Su. Natural ventilation design for underground parking garages. Building and Environment, vol. 227 (2023), p. 109784.
  6. Z. Liu, H. Yin, S. Ma, et al. On-site assessments on variations of PM2.5, PM10, CO2 and TVOC concentrations in naturally ventilated underground parking garages with traffic volume. Environmental Pollution, vol. 247 (2019), p. 626–637.
  7. A. Duci, K. Papakonstantinou, A. Chaloulakou, N. Markatos. Numerical approach of carbon monoxide concentration dispersion in an enclosed garage. Building and Environment, vol. 39 (2004) No. 6, p. 1043–1048.
  8. W.K. Chow. On ventilation design for underground car parks. Tunnelling and Underground Space Technology, vol. 10 (1995) No. 2, p. 225–245.