Graded Diagnosis of 110 kV Porcelain Insulator Degradation based on Spatial Electric Field Distribution
A graded diagnosis method for 110 kV porcelain insulator degradation is proposed based on spatial electric-field distribution. The study is limited to a seven-disc 110 kV porcelain suspension insulator string so that modeling, feature extraction, and validation remain focused on one practical operating scenario. First, a finite-element baseline model is built for the healthy 110 kV porcelain insulator string to obtain the axial electric-field distribution pattern. Second, continuous RMS samples acquired by an unmanned-aerial-vehicle-mounted all-fiber electric-field sensor are converted into electric-field intensity, interpolated, divided into seven adaptive segments, and represented by trimmed-mean disc-level features. Finally, a dual-index decision rule combining a dynamic-rate ratio and a standard-deviation ratio is developed, followed by a four-level disc degradation grading model. Laboratory experiments on 110 kV seven-disc strings show that the method can locate degraded discs and provide severity grades. In the tested cases, the recall is higher than 94.5%, the false alarm rate is below 5.5%, and a single analysis takes less than 15 s.
References
- Salem, A. A., Lau, K. Y., Ishak, M. T., Abdul-Malek, Z., Al-Gailani, S. A., Al-Ameri, S. M., Mohammed, A., Alashbi, A. A. S., & Ghoneim, S. S. M. (2022). Monitoring porcelain insulator condition based on leakage current characteristics. Materials, 15(18), 6370. https://doi.org/10.3390/ma15186370.
- Rahman, E. U., Zhang, Y., Ahmad, S., Ahmad, H. I., & Jobaer, S. (2021). Autonomous vision-based primary distribution systems porcelain insulators inspection using UAVs. Sensors, 21(3), 974. https://doi.org/10.3390/s21030974.
- Zhang, Z., Zhang, H., Jiang, X., Zhou, C., Liu, R., & Li, Y. (2025). Detection of zero-value insulators in ±800 kV DC porcelain strings based on spatial electric field variation. Journal of Electrostatics, 138, 104206. https://doi.org/10.1016/j.elstat.2025.104206.
- Wu, S., Wang, L., Song, B., & Gao, J. (2024). Live-line detection of deteriorated insulators on overhead transmission lines based on electric field distribution. IEEE Sensors Journal, 24(2), 1687–1695. https://doi.org/10.1109/JSEN.2023.3332849.
- Zhang, D., Zhang, Y., Liu, H., Cheng, Y., Wan, W., Gao, T., Han, X., Zhang, Z., & Jiang, X. (2024). Research on the prediction method of porcelain insulator pollution degree based on electric field monitoring. Electric Power Systems Research, 233, 110488. https://doi.org/10.1016/j.epsr.2024.110488.
- Zhou, J., Li, X., Xu, Z., Zhu, Y., Li, X., & Ma, H. (2021). Influence of porcelain insulator deterioration on axial electric field distribution of transmission line insulator string based on finite element method. Insulating Materials, 54(10), 79–83. https://doi.org/10.16790/j.cnki.1009-9239.im.2021.10.012.
- Ghermoul, O., Benguesmia, H., & Benyettou, L. (2023). Finite element modeling for electric field and voltage distribution along the cap and pin insulators under pollution. Diagnostyka, 24(2), 1–9. https://doi.org/10.29354/diag/159517.
- Al-Karawi, S., & Al-Taie, A. (2024). Superhydrophobic coating for enhancing porcelain insulators performance under pollution conditions. e-Prime—Advances in Electrical Engineering, Electronics and Energy, 8, 100515. https://doi.org/10.1016/j.prime.2024.100515.
- Li, Y., Wu, H., Liu, S., Liu, X., Zhao, Y., Chen, R., & Yang, G. (2023). Effect of sand covering on surface electric field and potential distributions of 110 kV porcelain insulator. Insulating Materials, 56(5). https://doi.org/10.16790/j.cnki.1009-9239.im.2023.05.014.
- Li, Y., Yang, G., Wu, H., Kang, W., Xiang, Z., Liu, S., Zhang, J., & Zhao, Y. (2023). The variation law of surface potential and electric field of porcelain insulator in suspended sand and dust environment. Insulating Materials, 56(8), 87–93. https://doi.org/10.16790/j.cnki.1009-9239.im.2023.08.013.
- Ramnarine, V., Liu, F., Peesapati, V., & Djurović, S. (2026). Packaged FBG + PMN-PT sensor for contactless electric field monitoring of overhead line insulators. IEEE Sensors Journal, 26(7), 9851–9860. https://doi.org/10.1109/JSEN.2026.3661239.
- Salem, A. A., Al-Gailani, S. A., Amer, A. A. G., Alsharef, M., Bajaj, M., Zaitsev, I., Ngah, R., & Ghoneim, S. S. M. (2024). Classification of RTV-coated porcelain insulator condition under different profiles and levels of pollution. Scientific Reports, 14, 22759. https://doi.org/10.1038/s41598-024-73520-7.